CEAG Notlichtsysteme GmbH
48
Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
displaying
– Time and date (line 0)
– Operating mode (line 1)
– Fault information
(line 2)
– Device name (line 5)
Keypad
ESC key <ESC>
Menu key
ok key <ok>
and cursor keys
Memory card for saving and data
transmission of test log and parame-
ter settings
Control module
CU S
+
1
Test & status menu
1.1
Start functiontest
1.2
Sum failure info
1.3
Circuit state
1.4
Luminaire state
1.5
DLS/TLS/3PhW state
1.6
Relay state
Main menu
Main screen (Example)
1.
Test & status menu
2.
Block & reset alarms
3.
Basic settings
4.
DLS/TLS setup
5.
Circuit setup
6.
Luminaire setup
7.
Logbooksetup
Multi-Master Mode M3:
In Multi-Master Mode the following functions are
possible to activate:
– Start FT
– Substation-status (display)
– Block/release device
– Date/Time (set)
– Automatic FT (specify)
Previously, the substation needs to be found
in the menu «Main settings /Substation setup».
Before the execution of the command there
is a request in the Mulit Master Mode if this
system-no. or all systems of one group should
execute this command.
The M3 function can only be executed when all
control units are interconnected over the CG-S
bus and no CGVision is used.
If password protection is activated,
then only the main screen and the main
menu options “1 Test and Status Menu”
and “2 Block ,Reset” are accessible with-
out entering a password.
The controller software automatically
returns to the main screen if no entry is
made within 180 seconds.
The graphic display backlighting goes
off if no entry is made within 180 sec-
onds.
Pressing any key switches the backlight-
ing on again.
The contrast and brightness (back-
lighting of the graphic display) can be
adjusted in the main screen when the
<ok> key is pressed:
<ok> +
/
: contrast adjustment
<ok> +
/
: brightness adjustment
These parameters can also be set with
menu option “3.10 Display Setting” in
menu “3 Basic Settings”.
Here the parameters can be numerically
set as percentages.