52
Operating
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
8.4.2 Menu 2: “Block, reset”
Overview:
Main menu
Test & status menu
Block,reset
Basic settings
DLS/TLS Setup
Circuit setup
Luminaire setup
Memory card
Menu 2
Block device
Release device
Manual reset
Selection of
menu options
with the
keys
<ok>:
confirm selec-
tion
<Menu>: can-
cel and return
to the previous
menu (any
changes
entered are
saved)
<ESC>: cancel
and return to
the previous
menu (any
changes en-
tered are not
saved)
flashing input
prompt
<ok>
Menu 2.1:
(Menu 2.3: only directly at the station)
<ok> initiates the function if this ope-
ration has been activated in the menu
option «Basic settings»:
Following a mains power failure, normal
operation will not be resumed automati-
cally when mains power is restored if
the “Manual reset (On)” option has been
Block device
Release device
Manual reset
Block device
Release device
Manual reset
This device
all devices
Device address 01
Device name
Block device
Release device
Manual reset
<ok> initiates the function:
The selected stations will be swichted free
and restart operation.
activated (menu «Basic settings/Manual
reset»).
This guarantees that the emergency light-
ing remains on until it is ensured that the
general lighting has been switched on
again, e.g. in a cinema.
Selection with the buttons
bet-
ween the displayed options.
Selection of a AT-S
+
system with
Device address referes to search
results in the substation setup
menu 3 «Basic settings»
<ok>
Menu 2.2:
This device
all devices
Device address 01
Device name
<ok> initiates the function:
All functions are cancelled;
all outputs will be isolated!
In case of mains failure occures no emer-
gency operation.
These must be additionally separated on
all poles before maintenance work in end
circuits. (see 10.3 Enabling of end circuits
with maintenance work)