CEAG Notlichtsysteme GmbH
25
Construction and Function
Assembly and Operating Instructions
Automatic Test System AT-S
+
with STAR
+
Technology
4.4.6 External DLS/3Ph-bus-module and ext. DLS/3Ph-bus-module inverse
This electronic monitoring module acts as a (light-)switch scan and/or for monitoring of the phases of a mains
power supply (e. g. in a subdistribution board):
Luminaires of the general lighting and the safety lighting are switched in mains operation in accordance with the
switch position and the settings for the controller CU-S
+
.
In emergency operation (e. g. after a message about a breakdown of monitored phases of the mains power supply)
the circuits of the safety lighting will be operated according to the settings of the controller CU-S
+
.
DLS/3Ph-bus-modules are available in two performances which only differ in view of the switching perfor-
mance (inverting of the DLS circuits)!
Technical Data
Mains supply for the modules
– Device: 24 V DC (19 ... max. 30 V)
– Cable type: 4 x 2 x 0.8 mm IY(ST)Y, Twistet Pair screened (minimal standard).
– Current consumption: 20 mA (15 ... 25 mA) with 8 connected circuits
Bus connection
– RS 485
– Rated voltage U
n
= 24 V DC
– Cable type: 4 x 2 x 0.8 mm IY(ST)Y, Twistet Pair screened (minimum requirements).
– Connection terminal A, B, SE
Input circuits
– up to 8 potential-free disconnected
– Rated voltage U
n
= 230 V
Switching performance of DLS-circuits DLS/3Ph/ Switching performance of DLS circuits DLS/3Ph inverse
U < 138 V = OFF
U < 138 V = ON
U > 195 V = ON
U > 195 V = OFF
Switching performance of 3Ph circuits
(same for DLS/3Ph module and DLS/3Ph module inverse)
U < 138 V = OFF
U > 195 V = ON
Application:
Two operation modes are available:
(pure) DLS-mode
(mixed) DLS/3Ph-mode
With a dispatcher (pos. 5) the operation mode can be chosen.
Assembly in the subdistribution board
of the monitored circuits due to the low laying effort for the illumination circuits (compare «Mounting and
connection of external bus modules»).
Assembly in the control cabinet AT S
+
C (AT S
+
S)
due to reasons for simplification of the maintenance (compare «Mounting and connection of external
modules»).
Application-environment
Protection class / -category:
IP20 / I
Ambient temp.:
-10 ... +40°C
Notes:
Please observe the regulations for bus-technology and screening on the following pages.
For planning and application of the modules we advice to observe the technical documentations attached to
the modules and the catalogues ofCEAG Notlichtsysteme GmbH!
Optically, the inverse and the non-inverse DLS/3Ph-module only differ in the printed description and the item
number!
Due to break or short-circuit of the RS485-bus line all connected luminaires will be switched on!