background image

1

INSTA LL ATION INSTRUC TIONS

Retrofit of Spectra K-frame with ABB Tmax XT7 breaker 

Single Mount (Bolt-On kits) 

General

These instructions are applicable to retrofit of Spectra K-frame with ABB Tmax XT7 breaker.
Table 1 lists the parts included in the bolt-on circuit breaker kits for single branch configurations.

WARNING

Danger of electrical shock or injury. Turn OFF power ahead of the panel board or switchboard before working inside the equipment
or removing any component. Equipment is to be installed and maintained by properly trained and qualified personnel only.

Installation

Numbers in brackets in the following instructions and figures refer to the item numbers in table below.

Item

Part

Description

Qty.

1

1/4 - 20 x 1.50” carriage bolt

6

2

1/4 - Belleville Washer

6

3

1/4 - 20 Nut

6

4

Breaker mounting bracket

1

5

Thread-forming screw #10-32

6

6

Flange Nut - Thread size 3/8-16

6

7

Socket Head Screw # 10-32 UNF x 4 IN

2

8

L-Shaped Barrier

1

9

Filler plate

1

10

Busbar Link assembly - C phase

1

Item

Part

Description

Qty.

11

Busbar Link assembly - B phase

1

12

Busbar Link assembly - A phase

1

13

Kit-Foldable Handle, XT7 (for panel 

application)

1

14

Terminal Cover, XT7 (HTC)

1

 

Item

Part

Description

1

Torque wrench

Retrofit Kit

Required Tools

Below listed tools are required for installation


Table 1. Retrofit kit

Summary of Contents for Spectra K-frame

Page 1: ...ied personnel only Installation Numbers in brackets in the following instructions and figures refer to the item numbers in table below Item Part Description Qty 1 1 4 20 x 1 50 carriage bolt 6 2 1 4 Belleville Washer 6 3 1 4 20 Nut 6 4 Breaker mounting bracket 1 5 Thread forming screw 10 32 6 6 Flange Nut Thread size 3 8 16 6 7 Socket Head Screw 10 32 UNF x 4 IN 2 8 L Shaped Barrier 1 9 Filler pla...

Page 2: ...d forming screws 5 torque the screws to 35 lb in Refer figure 5 STEP 6 Prepare L shaped barrier assembly Fold L shaped barrier 8 as shown in figure 6 and fix the breaker isolation base plate sup plied with breaker kit to the adhesive surface of L shape barrier 8 as shown in figure 6 4 8 5 Folded Breaker side Adhesive side Align holes Breaker isolation backplate To mate with mounting plate 2 STEP 1...

Page 3: ...eaker with L shaped barrier assembly from STEP 6 Refer figure 7a Tighten Socket head screw 7 and flange nut 6 torque the screw 7 to 22 lb in Torque the flange Nut 6 to 160 lb in Refer figure 7b and 7c Figure 7a Installation of breaker and L shaped barrier assembly 7 2x L shaped barrier with isolation base plate From STEP 6 6 STEP 10 Install the filler plate 9 to panel with thread forming screw 5 t...

Page 4: ...ntents of this doc ument without prior notice With regard to purchase orders the agreed particulars shall prevail ABB AG does not accept any re sponsibility whatsoever for potential errors or possible lack of information in this docu ment abb com We reserve all rights in this document and in the subject matter and illustrations con tained therein Any reproduction disclosure to third parties or uti...

Reviews: