Defines the integral gain for frequency controller 1. See
Frequency Controller Proportional Gain Kp1
(Pr
65
).
Defines the time constant for the filter applied to the output of the frequency estimator system.
Spin Start Boost
(Pr
69
) is used by the algorithm that detects the frequency of a spinning motor when
the drive is enabled and
Catch A Spinning Motor
(Pr
33
)
≥
1. For smaller motors the default value of
1.0 is suitable, but for larger motors
Spin Start Boost
(Pr
69
) may need to be increased.
If
Spin Start Boost
(Pr
69
) is too small the drive will detect zero speed whatever the frequency of the
motor, and if
Spin Start Boost
(Pr
69
) is too large the motor may accelerate away from standstill when
the drive is enabled.
This parameter is the output of the PID controller. For further information, refer to the
Parameter
Reference Guide.
Proportional gain applied to the PID error. For further information, refer to the
Parameter Reference
Guide.
66
Frequency Controller Integral Gain Ki1
RW
Num
US
OL
Ú
Ö
RFC-A
0.00 to 655.35 s
2
/rad
0.10 s
2
/rad
67
Sensorless Mode Filter
RW
Txt
US
OL
Ú
Ö
RFC-A
4 (0), 5 (1), 6 (2), 8 (3), 12 (4),
20 (5) ms
4 (0) ms
69
Spin Start Boost
RW
Num
US
OL
Ú
0.0 to 10.0
Ö
1.0
RFC-A
70
PID1 Output
RO
Num
ND
NC
PT
OL
Ú
±100.00 %
Ö
RFC-A
71
PID1 Proportional Gain
RW
Num
US
OL
Ú
0.000 to 4.000
Ö
1.000
RFC-A