38
Unidrive M300/HS30 Quick Start Guide
Issue Number: 7
Defines which value of keypad control mode reference is displayed at power-up.
Defines the mode used by the ramp system.
0:
Fast ramp
1:
Standard ramp
2:
Standard ramp with motor voltage boost
3:
Fast ramp with motor voltage boost
Fast ramp is linear deceleration at programmed rate, normally used when a braking resistor is
installed.
Standard ramp is controlled deceleration to prevent DC bus over-voltage trips, normally used when
there is no braking resistor installed.
If a high motor voltage mode is selected, deceleration rates can be faster for a given inertia but motor
temperatures will be higher.
Setting Pr
29
to 0 allows the user to disable the ramps. This is generally used when the drive is
required to closely follow a speed reference which already contains acceleration and deceleration
ramps.
27
Power-up Keypad Control Mode Reference
RW
Txt
ND
NC
PT
US
OL
Ú
rESEt (0), LASt (1), PrESEt (2)
Ö
rESEt (0)
RFC-A
Value
Text
Description
0
rESEt
Keypad reference is zero
1
LASt
Keypad reference is the last used value
2
PrESEt
Keypad reference is copied from
Preset Reference 1
(Pr
18
)
28
Ramp Mode Select
RW
Txt
US
OL
Ú
Fast (0), Std (1), Std.bst (2),
Fst.bst (3)
Ö
Std (1)
RFC-A
29
Ramp Enable
RW
Bit
US
OL
Ú
Ö
RFC-A
Off (0) or On (1)
On (1)