Unidrive M300/HS30 Quick Start Guide
39
Issue Number: 7
* Only a value of 3 or 4 in this parameter is saved.
If Pr
30
is equal to 1 or 2, this value is not transferred to the EEPROM or the drive. If Pr
30
is set to a
3 or 4 the value is transferred.
For further information, please refer to Chapter 9
NV Media Card Operation
on page 61.
Defines how the motor is controlled when the run signal is removed from the drive.
See the
Control User Guide
for further information.
Open-loop:
Set to 1 to enable Dynamic V to F mode in open-loop mode only.
0:
Fixed linear voltage to frequency ratio (constant torque - standard load)
1:
Voltage to frequency ratio dependant on load current. This gives a higher motor efficiency.
30
Parameter Cloning
RW
Txt
NC
US*
OL
Ú
NonE (0), rEAd (1), Prog (2), Auto
(3), boot (4)
Ö
NonE (0)
RFC-A
Parameter string
Parameter value
Comment
NonE
0
Inactive
rEAd
1
Read parameter set from the NV Media Card
Prog
2
Programming a parameter set to the NV Media Card
Auto
3
Auto save
boot
4
Boot mode
31
Stop Mode
RW
Txt
US
OL
Ú
CoASt (0), rP (1), rP.dc I (2),
dc I (3), td.dc I (4), dis (5)
Ö
rP (1)
RFC-A
CoASt (0), rP (1), rP.dc I (2),
dc I (3), td.dc I (4), dis (5), No.rP (6)
Value
Text
Description
0
CoASt
Coast stop
1
rP
Ramp stop
2
rP.dc I
Ramp stop + 1 second dc injection
3
dc I
Injection braking stop with detection of zero speed
4
td.dc I
Timed injection braking stop
5
dis
Disable
6
No.rP
No ramp (RFC-A mode only)
32
Dynamic V To F Select / Flux Optimization Select
RW
Num
US
OL
Ú
0 to 1
Ö
0
RFC-A