
System Configuration
2–16
976-0043-01-01
The negative ends of the two “strings” of batteries must be jumpered
together to become common with each other.
Likewise, the positive ends of the two “strings” must also be
jumpered together so that they are also common with each other.
Shunts near the
inverter
Losses from the cables will cause each inverter to measure slight
differences in actual voltages, in spite of having the battery bank common
to both inverters. It is easy to have the DC negatives common closer to the
inverters if an in-line metering shunt is installed near the inverters before
the negative cables attach to the negative battery terminal.
Jumpers
The use of optional bonding jumpers can improve how each inverter
measures the DC voltage for decisions when charging amperages should
be reduced as the batteries become charged. The bonding jumpers allow
the inverters to agree better on what the voltage actually is. The longer the
DC cables are, the more likely you will need bonding jumpers.
Shunts near the
batteries
If a shunt is installed closer to the battery bank than the inverters, a
bonding jumper should be installed from one inverter’s negative terminal
to the other inverter’s negative terminal. By using a negative bonding
jumper and/or a metering shunt near the inverters, the inverters will have
a better zero volt (DC negative) reference to measure the DC voltage.
DC disconnects
The DC positive is more difficult due to the need to have DC disconnects
in each cable for the inverters. The primary reason for the DC disconnects
is for overcurrent protection for the cable it is installed in. By using a
positive bonding jumper the inverters will have a more accurate DC
positive reference to measure the DC voltage.
Bonding jumpers in
positive line
A bonding jumper may be installed from one inverter’s positive terminal
to the other inverter’s positive if a warning is placed near the DC
disconnects. This means that either DC disconnect can energize both
inverters while the other DC disconnect is not yet turned on. This is called
"backfeeding" a disconnect or circuit breaker. The 2002 NEC,
Section 404.6, C, Exception, allows switches to be backfed if a warning
such as the following is permanently marked on or adjacent to the
disconnect switches. A sample of this warning label is provided in
Figure
2-2
.
These labels are not available or provided by Xantrex, but may be
available from your local electrical warehouse.
Figure 2-2
Sample Warning Sticker for Backfeed Conditions
WARNING: Shock Hazard
Load side terminals may
be energized by
backfeed.
Not provided by Xantrex.
May be available at your local
electrical warehouse.
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......