Menu Item Descriptions
976-0043-01-01
7–9
Silent mode will begin after the charge routine has finished the bulk/
absorption charge and if the silent charge has been selected (from Menu
item
12A Finish Stage
). After entering the Silent mode, there will be a
minimum 60 second delay, then the inverter will monitor the battery
voltage to determine if the voltage is at or above the
20A Refloat High
Volts DC
setting or if the voltage has fallen to or below the
20B Refloat
Low Volts DC
setting.
If the battery voltage has reached one of these refloat Vdc settings
(
20A Refloat High Volts DC
or
20B Refloat Low Volts DC
) then the
inverter will come out of silent and begin to maintain the batteries at the
float voltage level.
If the battery voltage tries to fall below the float level, the inverter will
use current from the utility grid connected to the AC1 input to continue to
maintain the float voltage level.
External charging
sources
If some external current (renewable energy source) is used to increase the
battery voltage above the float voltage level, the inverter will use this
excess power above the float voltage requirements to power the inverter
output loads.
If the external current source provides more current that what is needed to
maintain the batteries at the float voltage and power the inverter loads, the
battery voltage will rise.
The inverter will continue to maintain the batteries at the float voltage
level until the
20D Must Float Time Min
time has expired and the
current (as read on the
04C INV/CHR Amps AC
meter display) has
fallen below the
20C Float Done Amps
setting. At this time, the inverter
will return to the Silent mode.
If AC power is lost, after it has returned, the inverter will complete
another Bulk and Absorption charge to the battery and again return to the
silent stage.
Advantages
The advantage of the Silent stage is slightly less power consumption
under most conditions and quieter operation since the battery charger is
off most of the time.
Disadvantage
The disadvantages of Silent charge is the loss of the natural power
conditioning ability of the inverter, the ability to provide the AC load
support (except during the time that the inverter is charging) and a longer
transfer to inverter power from the loss of utility power. These
disadvantages are only present when the inverter is not charging batteries.
Summary
Silent comes on based on DC volts as programmed in
20A Refloat High
Volts DC
and
20B Refloat Low Volts DC
(after 60 second delay)
Silent goes off based on time
20D Must Float Time Min
, then amps
20C Float Done Amps
.
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......