Troubleshooting
9–8
976-0043-01-01
05G Input Relay
Failure
The AC transfer relay is
bad or an AC source was
wired directly to the AC
output.
Disconnect the inverter’s output wiring. If error
continues, have unit serviced.
05H Gen Failed To
Start
Indicates that six “auto
generator start attempts”
have occurred without
successfully starting the
generator.
Voltage has not reached
80 Vac during the
25D Max Cranking
Seconds
period.
Voltage did not maintain
> 80 Vac for the majority
of time while the inverter
was charging.
Reset the auto-generator control system by selecting
OFF at the
02A Generator
menu.
Verify that when the generator is running (manually
started) that there is voltage on the AC2 input
terminals inside the inverter’s AC access door.
If you do not have an automatic start generator that
is started by the inverter, leave it in the OFF
selection.
If you do have an automatic start generator that is
started by the inverter, test by selecting ON.
Measure the AC voltage on the AC2 input terminals
while the generator is starting. Check the setting at
25D Max Cranking Seconds
. Tune up generator if
necessary.
Measure AC voltage on the AC2 input terminals
while generator is running. Check for poor
connections or too small of wires between the
generator and inverter. Tune up generator if
necessary.
05I Gen Stopped Due
To V/F
The generator was
running but was not
operating within the
voltage or frequency
tolerances and was not
able to connect.
Check the generator’s output voltage and frequency.
Ensure that
13C Input Upper Limit VAC
and
13D Input Lower Limit VAC
are set correctly.
Error LED is flashing
and there is no error
under
05 Error Causes
Menu
.
AC source frequency is
just out of tolerance
(53–57 Hz or 63–67 Hz).
No problem with AC source or inverter. The error
LED is a visual indicator to fine tune your AC
frequency. This error does not affect operation.
Message
Problem
Solution
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......