Menu Item Descriptions
976-0043-01-01
7–19
Manual Generator Control
The generator equipped for remote starting capabilities can be remotely
started by selecting ON from
02A Generator
. If the generator started in
this manner, the
02C GEN Start Volts/Manual
menu item will display
YES.
The generator will continue to run unless one of the following procedures
is performed:
1. Manual Stop – Manually stop the generator by selecting OFF from the
02A Generator
menu item.
The generator will receive the stop command immediately if manually
stopped
2. Auto Stop – Select AUTO directly (without allowing the cursor to pass
through OFF) will allow the generator to automatically stop. It will
shut off once the BULK and ABSORPTION stages of the battery
charging have completed, thus fully recharging the batteries.
Automatic Generator Control
The generator can be programmed to start and stop automatically based on
the following scenarios:
•
AC Current
•
Battery Voltage
•
Time of Day
•
Required Exercise Period
AC Current
The generator starts whenever the current demand through the inverter to
the AC loads remains above the
26A Load Start Amps AC
setting for the
selected
26B Load Start Delay Min
period. The current can be monitored
by the
04E Load Amps AC
menu item under the
04 Meters menu
.
The generator will start, unless the timer is in the “quiet time” period, at
which time it will only start if the
26G Read LBCO 30 Sec Start Vdc
setting is reached.
Whenever the generator starts automatically, based on load amps, it will
shut off once the load current drops below the
26A Load Start Amps
value for the selected
26B Load Stop Delay Min
period.
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......