Advanced Setup
7–34
976-0043-01-01
26F 15 Min Start Volts DC
This menu item sets the battery’s DC voltage level which initiates
automatic generator starting whenever the voltage drops below this
setting continuously for 15 minutes. This item is not temperature
compensated and is defeated during the quiet time period set in the
24 Generator Timers Menu
.
26G Read LBCO 30 Sec Start
This menu item monitors the
11C Low Battery Cut Out VDC
level and
initiates automatic generator starting whenever the voltage drops below
the LBCO setting continuously for 30 seconds. The LBCO setting is not
temperature compensated. This display is linked and adjusted in menu
11C Low Battery Cut Out VDC
. The 30 second start attempts to auto
start the generator even if the quiet time (as set in menu
24 Generator
Timers Menu
) is enabled. This is a read-only display.
27 Save/Restore Settings Menu
This menu provides the means to:
•
save recently programmed settings,
•
restore previously programmed settings, or
•
to restore factory default settings.
27A Push INV now to Save Settings
This menu item provides the means to save settings currently
programmed into the inverter.
To save settings:
1. When
27 Save/Restore Settings
Menu is displayed, press the
button to select
27A Push INV Now to Save Settings
.
2. Press the red INV button to save the settings.
26F 15 Min Start
Volts DC
26G Read LBCO 30
Sec Start
27 Save/Restore
Settings Menu
Note:
The settings in this menu are identical to Menu 14. Saving or
restoring settings at either menu will apply to all menu settings (Basic
and Advanced).
27A Push INV Now
to Save Settings
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......