Menu Item Descriptions
976-0043-01-01
7–23
24D Quiet Time End h:m
This menu item ends the quiet time, after which the generator can be
started if required, if an auto-start condition exists.
To completely disable the quiet-time feature, set the start and stop times to
the same value.
The generator exercise timer uses this setting to determine when to start
the generator exercise. The generator will start and run for the time set in
menu
24F Gen Exercise Time Min
at the end of the quiet time. If the
selection in menu
24E Gen Exercise Period Days
has been set for 01
(every day), the generator will run every day at the end of the quiet time.
To disable the generator exercise system, set the number of days to zero.
The set points for this menu item change in 10-minute increments.
24E Gen Exercise Period Days
This menu item sets the maximum number of days between generator
operation. When the internal counter reaches the number of days set, the
generator starts (at the end of the quiet time setting). If the generator is
run for 5 minutes at any time during this period, this counter resets, and
the period starts again. If the menu item is set to 1, the generator runs
every day at this time.
Setting this value to 00 disables this function.
24F Gen Exercise Timer Min
This menu item sets the number of minutes the generator will perform an
exercise run after being started by the setting in menu item
24E Gen
Exercise Period Days
.
The set points for this menu item change in 1-minute increments.
24G Gen Cooldown Timer Min
This menu item sets time the generator is allowed to run unloaded (the
inverter is now powering the loads). It is good practice to allow the
generator to run unloaded for a period of time, to properly cool off before
shutting it down. Refer to the manufacturer’s specifications on cool down
time.
The set points for this menu item change in 1-minute increments.
24E Quiet Time
End h:m
24E Gen Exercise
Period Days
24F Gen Exercise
Timer Min
24G Gen Cooldown
Timer Min
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......