Operation
8–26
976-0043-01-01
05C Heatsink Overtemp
If “yes” is visible in this display, the power transistors have exceeded their
designed operating temperature and the inverter is shut off.
When this error condition occurs, if the unit is operating as a battery
charger, the inverter stops charging to prevent further overheating.
In the inverter mode, overheating can be caused by powering an excessive
load for too long. Blocked air vents or a fan failure can also cause this
condition.
When the inverter has this error, AC current from the source (utility grid
or generator) is passed through the inverter to power the loads. Power
management features provided by the inverter are not available with this
error.
The inverter automatically resets when it has cooled.
05D Low Battery Voltage
If “yes” is visible in this display, the battery voltage has dropped below
the
11C Low Battery Cutout VDC
setting continuously for the
11D LBCO Delay Minutes
period.
When a battery protection fault occurs (due to either a high or low battery
charge condition), the yellow STATUS LED will flash. If this condition
continues without being corrected then the inverter will shut down and the
red ERROR LED will illuminate solidly.
After shutting down from a low battery protection condition, the inverter
will return to normal operation when:
•
the AC source power is restored and the inverter operates as a battery
charger,
•
the inverter is manually restarted by pushing the red INV button on
the control module to access the
01A Inverter
menu item and
selecting OFF, then SRCH or ON from the display, or
•
the battery voltage rises above the setting in menu setting
11B Low Battery Cut In VDC
.
AC current is still passed-through to the load if an AC source within
acceptable tolerance is available.
05C Heatsink
Overtemp
YES
05D Low Battery
Voltage
YES
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......