Menu Item Descriptions
976-0043-01-01
6–15
12 Battery Charging Menu
Battery Charging parameters are programmed in
12 Battery Charging
Menu
, using the following menu items. Some of the menu items will
require making calculations. Others just require making selections
between the setpoints.
The voltage level settings should be adjusted with the battery at a
reference temperature of 25 °C.
WARNING: Explosion Hazard
Only flooded or vented batteries should be equalize-charged.
Hydrogen and oxygen gases are produced when batteries are
equalize-charged. Provide adequate ventilation and remove all
sources of ignition to prevent explosion.
CAUTION: Damage to DC Loads and Batteries
DC loads should be disconnected from the batteries during
equalization charging to protect DC loads from high battery
voltages.
Equalization was designed for use on standard, liquid
electrolyte (lead acid) batteries. Other battery types can be
permanently damaged if equalized. If you have sealed or gel
cell batteries, do not use the equalization charging function
without first checking with the battery manufacturer.
Batteries will heat up when equalize charging. Always monitor
the battery temperature in
04K Battery Temp Degrees C
and
shut down the charger if the temperature exceeds the
manufacturer’s specifications. The BTS must be installed for
the inverter to monitor battery temperature.
12 Battery
Charging Menu
Important:
Please consult your system designer or battery
manufacturer for specific battery charging recommendations.
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......