Advanced Setup
7–32
976-0043-01-01
25B Gen Warm-up Seconds/minutes
This menu item sets the number of seconds or minutes the generator is
allowed to warm up before the load is connected and the battery charger
started. If the generator is located in a cold location, a longer setting may
be required.
25C Pre Crank Seconds
This menu item sets the number of seconds the system delays engaging
RY8 (the crank signal relay) once relay RY7 is engaged. Also if GS is
selected from
25A RY7 Mode
, this setting will allow selection of the
delay time between RY7 disengaging and RY8 engaging. If this number is
even, the delay is immediate. If the number is odd the delay is three
seconds.
Refer to
“Automatic Generator Control” on page 7–19
for more
information. This period may also be the amount of time the glow plug is
ON if it is connected to the automatic start system.
25D Max Cranking Seconds
This menu item sets the maximum number of seconds the starter is
cranked during the starting sequence by engaging relay RY8.
Guidelines for setting this menu item:
•
If GS or RN1 (RY7 Mode) are selected, RY8 will disengage when the
generator AC output is sensed (> 80 Vac) on the inverters AC2 input.
•
If RN2 (RY7 Mode) is selected, RY8 will stay engaged (crank) for the
entire time set in menu
25D Max Cranking Seconds
.
25E Post Crank Seconds
This menu item sets the number of seconds after an unsuccessful crank
attempt, the system will delay before attempting another auto start
sequence. If the generator has not started, this sequence is repeated up to
5 times.
This period is provided to allow the starter motor to cool down. It can also
allow generators with built-in warm-up delay contactors to provide AC
output before the inverter attempts a re-crank cycle.
25B Gen Warm-up
Seconds/Minutes
25C Pre Crank
Seconds
25D Max Cranking
Seconds
25E Post Crank
Seconds
Содержание SW 2524
Страница 1: ...Sine Wave Plus Inverter Charger Owner s Manual Smart choice for power www xantrex com SW 2524 SW 2548...
Страница 2: ......
Страница 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Страница 24: ...xxii...
Страница 26: ...xxiv...
Страница 82: ...2 48...
Страница 101: ...DC Wiring 976 0043 01 01 3 19 Figure 3 9 BTS RJ11 Port Location and Installation BTS RJ11 Port DC End of the Inverter...
Страница 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Страница 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Страница 126: ...3 44...
Страница 127: ...4 Functional Test Chapter 4 Functional Test explains how to conduct a functional test of the inverter...
Страница 132: ...4 6...
Страница 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Страница 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Страница 143: ...Menu Map 976 0043 01 01 5 11...
Страница 144: ...Navigation 5 12 976 0043 01 01...
Страница 145: ...Menu Map 976 0043 01 01 5 13...
Страница 146: ...Navigation 5 14 976 0043 01 01...
Страница 189: ...Menu Item Descriptions 976 0043 01 01 7 17 Figure 7 3 Relay 11 Wiring Example to Dual Inverters with Cooldown selected...
Страница 208: ...7 36...
Страница 240: ...8 32...
Страница 241: ...9 Troubleshooting Chapter 9 contains information and procedures for troubleshooting the Sine Wave Plus...
Страница 258: ...Inverter Specifications A 10 976 0043 01 01 Figure A 6 Time versus Current for the Sine Wave Plus 2548...
Страница 268: ...B 10...
Страница 286: ...C 18...
Страница 290: ...D 4...
Страница 294: ...E 4...
Страница 316: ...I 6...
Страница 319: ...Index 976 0043 01 01 IX 3...
Страница 320: ...Index IX 4 976 0043 01 01...
Страница 321: ......