3.2.3.10.- Stop Sounder Function.
This is option 9 of the SYSTEM CONFIGURATION menu. Within this menu we have the following
options:
ACTIVATION:
CONTINUOUS: "Stop Sounder" continues active after re-start up of the control panel.
RESET: "Stop Sounder" is automatically desactivated after re-start up of the control panel.
PERFORMANCE:
CONTINUOUS: "Stop Sounders" continues active although new signal alarm arrives to
control panel.
EVENT: "Stop Sounders" is deactivated when new signal alarm is received to control panel.
VIEW SET UP:
It is shown selection of "ACTIVATION" and "PERFORMANCE".
4.- Set-up.
4.1.- Prior verifications.
Prior to putting the
Lyon analogue
system
installation into operation, we must assure ourselves that
the installation is totally completed and we have all the data for its correct programming. For this it is
necessary to verify that the points shown below have been completed:
To have a 110~230V power source available dedicated to the fire protection system and that it is live
24 hours a day, seven days a week. (see chapter 2.1)
To have a set of two 12V batteries with a capacity between 7 and 24Ah depending on the number of
loops and load connected to the control panel. (to see chapter 2.3.1)
To verify that all the elements are connected to the installation.
To verify that there are no installation elements left unconnected or with connection errors that could
cause faults when putting into operation or deterioration of the
Lyon analogue system
elements.
Do not remove the covers until the installation is finished and clean.
To have a list with the total of connected elements of each type in each loop, see example in the
following table.
LOOP: 1
TYPE AMOUNT
A30XHA/S
25
A30XTA
2
A30XHTCO
47
PUCAY
36
SIRAY
3
MDAXY
6
MSTAY
1
KMAY
3
TOTAL
123
To have a list for each loop with the location, type and programming number of each element,
(sensor, button, relay module, technical signals module, analogue sirens, master module). This
programming number goes from 1 to 65533, see example in the following table:
Loop: 01
POINT Prog.
No.
Label
Type
Notes
1 12757
ROOM
101
A30XHA
2 12432
ROOM
102
A30XHA
3 4767
BUTTON
P1
PUCAY
4 6982
CORRIDOR
P1
KMAY