Digital fire detection control panel
LYON
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
54
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
www.cofem.com
3.2.2.10.- Welcome message
Option 7 of the main menu. From this option it is possible to change the welcome message. The
welcome message is the text that appears on the first line when the control panel is in standby. This
message can have a maximum of 40 characters, which we will enter by means of the control panel cursors
or an external keyboard.
3.2.2.11. - General reset.
Option 8 of the main menu. From this option it is possible to reinitialise the whole system. When
resetting the system all the control panel events are deleted, that is to say, alarms, faults and actuations. It
maintains the state of the out of service elements and/or zones.
3.2.2.12. - Review history
Option 9 of the main menu. In this menu we have 5 submenus: REVIEW COMPLETE HISTORY
,
REVIEW ALARMS
,
REVIEW FAULTS
,
REVIEW DISABLED ITEMS and
REVIEW RELAYS.
By means of the up and down cursors we will move through the various stored events. The events
are stored in chronological order from the most recent to the oldest, storing a maximum of 4095 events. Once
4095 events are stored, the control panel will automatically delete the oldest in order to store a new event.
Review complete history:
This enables each of the incidents detected by the control panel to be
reviewed, understanding by incident: disabled alarms, faults, zones and elements and actuations of
relays.
Review alarms:
This submenu is the same as the one to review the complete history except that is
exclusively for alarms.
Type of event Alarm type
N U M : 0 0 3
A L A R M
C A L L
P O I N T
L O O P :
0 1
P O I N T : 0 0 5
N . P r o g
:
0 0 0 0 1
Z O N E : 0 1
C . P A N E L : 0 1
0 1
⁄
0 1
⁄
0 7
1 2 : 0 1
L A B E L :
B : 1
P : 5
N S : 1
Review faults:
This submenu is the same as the one to review the complete history except that is
exclusively for faul
t.
Type of event Alarm type
N U M : 0 0 3
F A U L T
R E L A Y
S C
L O O P :
0 3
P O I N T : 0 0 3
N . P r o g
:
0 0 0 0 3
Z O N E : 0 1
C . P A N E L : 0 1
0 1
⁄
0 1
⁄
0 7
1 2 : 0 1
L A B E L :
B : 3
P : 3
N S : 3
Review disabled items:
This submenu is the same as the one to review the complete history except
that is exclusively for disabled items.
Type of event Alarm type
N U M : 0 0 1
D I S A B L E D
D I S. E L E M E N T
L O O P :
0 1
P O I N T : 0 0 1
N . P r o g
:
0 0 1 2 0
Z O N E : 0 1
C . P A N E L : 0 1
0 1
⁄
0 1
⁄
0 7
1 2 : 0 1
L A B E L:
B : 1
P : 1
N S : 1 2 0