1.5.5.2.- Operation and configuration
Each control panel in the network displays all information from other control panel and
interact with each other.
Once the power connection, proceed to the configuration in each of the control panels,
entering the number of each (without repeat). For this we perform the following sequence in control
panel menu (code 27): Menu (code 27)
4-
System configuration (code 9000)
8-
Communications
3-
Set control panel number.
After the configuration should perform a general reset at each control panel of the network.
For this we perform the following sequence: Menu (code 27)
8-
General reset.
A control panel in the network can perform the same functions as any normal control panel.
You can also perform the following functions on the rest of the control panels of the network:
Reset alarms and faults in the network control panels.
Reset all the network control panels.
Enable or disable without delay mode in all network control panels.
Enable or disable sirens stop in all network control panels.
Enable or disable the evacuation in all network control panels.
Enable or disable manual mode in all network control panels.
Disable the buzzer in all network control panels.
1.5.5.3.- Control panels network menu
In the control panels we can find the next specific control panels network menus:
VISUALIZE CONTROL PANELS: Visualize the set control panels.
RESET CONTROL PANEL NETWORK: Reset all the control panels in the network.
SPECIAL FUNCTIONS:
WITHOUT DELAY: Enable or disable all the delays of all the relays associated with
all network control panels.
OFF SIRENS: Enable or disable all the sirens stop associated with all network
control panels.
EVACUATION: Enable or disable all the relays associated with all network control
panels.
MANUAL MODE: Enable or disable manual mode in all network control panels.
SETUP CONTROL PANEL NUMBER:
ENTER CONTROL PANEL NUMBER.
CONTROL PANEL NUMBER: