During the startup process, the control panel may display various types of faults. For the
Lyon analogue
control panel
to work correctly, these faults must be resolved. For this, consult section 4.4 which describes
the main faults, the causes of them and the action to be taken to resolve them.
4.4.- Faults
4.4.1.- FAULTS IN CONTROL PANEL STARTUP
THE CONTROL PANEL DOES NOT TURN ON
(POWER SUPPLY AND BATTERY leds off, display
shows nothing)
Cause
Neither the 110~230V supply nor the batteries are providing the correct voltage to
the panel.
Solution
Check that there is 110~230V mains voltage in the terminal strip for connecting the A.C.
source. Connect fully charged 24V batteries (between 24V and 28V).
THERE ARE NO
LOOP CONTROLLERS
Cause
During the control panel's start-up process, the panel does not find any Loop
Controllers.
Solution
Turn off the control panel, leave it for one minute, and start it up again. If the same
message is still displayed, check whether the controller has been mishandled, ensuring
that it is correctly inserted in the back panel, and that the micro-switches are configured as
in the following table:
Controller 1:
Controller 2:
Controller 3:
Controller 4:
Controller 5:
Also consult section 3.2.1.1
CONTROLLER NOT FOUND WITH ADDRESS: 001 … 002 003 004 005
Cause
During the control panel's start-up process, the panel had not found the Loop
Controller with the number indicated.
Solution
Turn off the control panel, leave it for one minute, and start it up again. If the same
message is still displayed, check whether the controller has been mishandled, ensuring
that it is correctly inserted in the back panel, and that the micro-switches are configured as
in the following table:
Controller 1:
Controller 2:
Controller 3:
Controller 4:
Controller 5:
Also consult section 3.2.1.1
CONTROLLER NOT FOUND WITH ADDRESS: 011
Cause
During the control panel's start-up process, the panel has not found the Power
Source Controller.
Solution
Turn off the control panel, leave it for one minute, and start it up again. If the same
message is still displayed, check whether the controller has been mishandled, ensuring
that it is correctly inserted in the back panel.
When it is operating correctly, the led mounted in this power source controller should be
flashing.
Consult section 3.2.1.1