ENABLE AUTOEV.: Automatic evacuation is activated by this option.
DISABLE AUTOEV.: Automatic evacuation is deactivated by this option.
CONFIGURE DELAY: The delay period that occurs between the alarm being raised and the
siren and/or switch relays being activated is configured with this option. The maximum
delay is 9 minutes and 59 seconds.
AUTO EVACUATION SUMMARY: In this option we will be able to see the status of
automatic evacuation and its delay.
3.2.3.3.7- Added Delay Setup
This is option 7 of the CONFIGURE menu. This option is activated when it is introduced a time
between 1" to 9 min 59". When the first signal alarm is received, control panel actives corresponding
programmed delays. If operator press "Silence Buzzer" before programmed delay time is finished, all the
relays (including the sounder relay output in control panel) are additionally delayed with the value
"Additional delay". In this way, operator is allow to investigate alarm. If in any moment of the delays there is
a second signal alarm, all relays are activated immediately.
3.2.3.3.8- Fast Trigger Zone
This is option 8 of the CONFIGURE menu. The alarm signal input of any element defined in the zone
introduced in this option makes immediately activation of all control panel relays.
3.2.3.3.9- Send Zones to Repeaters
This is option 9 of the CONFIGURE menu. This option allows sending the configured zones to the
repeaters, of not realising it, the repeaters will only indicate the label of the point.
3.2.3.4.- Update date and time.
This is option 3 of the SYSTEM CONFIGURATION menu. Within this menu we have two options,
CHANGE DATE and CHANGE TIME. With the cursors we will be able to update the fields for both
options.
3.2.3.5.- Day/ Night times.
This is option 4 of the SYSTEM CONFIGURATION menu. Within this menu we have 5 submenus:
DAY TIME START, DAY TIME END, PROG. NIGHT MODE DAYS, DELETE NIGHT MODE PROG.
and PROGRAMMING SUMMARY.
The day/night mode serves to configure the activations of relays since they can have a different
operation for day and night. The day mode can be activated or deactivated independently for the different
days of the week.
DAY TIME START: The control panel will request the start time for the day mode.
DAY TIME END: The control panel will request the end time for the day mode.
PROG. NIGHT MODE DAYS: This option allows us to configure the control panel night
mode for the whole 24 hours of a day.
DELETE NIGHT MODE PROG.: This option deletes the configuration described in the
previous paragraph
PROGRAMMING SUMMARY: This option shows us the configuration of the night mode
day for the control panel.
3.2.3.6.- Put into test/ normal mode.
This is option 5 of the SYSTEM CONFIGURATION menu. Within this menu we have 3 submenus:
TEST MODE, NORMAL MODE and LIST ZONES.