Annex 2: Elements configuration Lyon / C-Lyon / Zafir
1. Introduction
The steps necessary to configure the Analogue Control Panel LYON are given below.
The analogue system includes the following elements:
Analogue
detectors
.
Optical
sensor
A30XHA
Heat sensor
A30XTA
Multi-sensor
A30XHTCO
Analogue
key
PUCAY
Master
module
KMAY
Relay
modules
1 relay
MDA1Y
2 relays
MDA2Y
Technical signals module
MSTAY
Relay and Technical signal module
MYOA
Loop
isolator
base
KABY
Analogue siren
SIRAY / SIRAYL
Each of these elements has a programming label. This number is assigned at the factory. When an element search
operation is conducted using the control unit, it finds all the loop elements, memorising the type of element and the
assigned programming number.
The basic purpose of this procedure is that, by conducting this search, all these numbers can be passed to the
control unit memory and for them to be assigned to the loop where the search was conducted.
NOTE: Before assigning a point, it is highly advisable to obtain the programming lists with all the data.
2. Keypad access
If the keypad has not been enabled, the only key that will work is the stop
BUZZER
button (
in the event of any
new incidents, the buzzer will be activated again
). The LYON / / C-LYON / ZAFIR system provides several
different access levels to the various internal functions. The first level of access controls the use of the keypad.
When any of the keys on the control panel are pressed, an access code will be requested: