Digital fire detection control panel
LYON
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
www.cofem.com
57
activation lists to be configured for each relay and they are configured by introducing a
first and last point (the points that are configured in the list are the all elements
consecutively from the first to the last entered point) in the same loop, except for the
crossed relay function which does not allow for activation lists.
VIEW CONFIGURATION: View the configuration of the relay and all its parameters.
R E L A Y :
R e l a y
M a n e u v e r
R e l a y
0 0 2
M D A 2 Y
M a n e u v e r
L o o p :
0 0 2
P o i n t : 0 0 3
D A Y
D e t e c t o r : Y e s
C a l l : Y e s
D e l a y :
0 0
N I G H T
D e t e c t o r : Y e s
C a l l : Y e s
VIEW DELAY LISTS: View the list of points configured for the relay.
3.2.3.3.3.- Configure alarm zones.
Option 3 of the CONFIGURE menu. In this menu we have the option of configuring the various
alarm zones into which we will divide the points of the control panel. When an alarm zone is
configured, it is not permissible to include a point in two different alarm zones.
Within this menu we have five submenus:
CONFIGURE ZONE: The control panel will request the loop number, the first and last
consecutive element included in the alarm zone list. We will be able to introduce 8 lists into
each alarm zone.
MODIFY LISTS: This option allows us to modify one of the alarm zone lists.
DELETE ZONE: The zone configuration is deleted.
LABEL: This provides a description of the zone with a maximum of 20 characters for its
identification in the installation.
VIEW CONFIGURATION: To view the list of points that are included in the alarm
zone.
Label Zone number
Z O N E :
B 1
D E T
1 Y 2 .
Z O N E :
0 0 1
B 0 1 : P 0 0 1 - 0 0 2
B 0 1 : P 0 0 6 - 0 0 6
Zone List
Zone List
3.2.3.3.4.- Configure element sensitivity.
Option 4 of the CONFIGURE menu. From this menu we can vary the sensitivity of the points
individually (indicating the loop and point number). There are three levels of sensitivity: HIGH, MEDIUM
AND LOW (all the sensors come with average sensitivity).
3.2.3.3.5.- Additional passwords.
Option 5 of the CONFIGURE menu. From this menu we can introduce an additional password for
the access level 2 and another one for the access level 3, except the numbers 00 and 0000. Whenever we
introduce a new password it deletes the one that had been previously entered. The standard Passwords that
the control panel have are: access level 2:
27
; and access level 3:
9000
).
3.2.3.3.6.- Configure auto-evacuation.
This is option 6 of the CONFIGURE menu. Within this menu we have four submenus: ENABLE
AUTOEV.,
DISABLE AUTOEV., CONFIGURE DELAY and AUTO EVACUATION SUMMARY.
Automatic evacuation is a function that activates the relays configured as sounder and/or switches if there is
an alarm in the system and the alarm has not been reset during the configured delay.