Digital fire detection control panel
LYON
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
70
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
www.cofem.com
If the incident in question is an
ALARM
, the user must verify whether it is real. If so, the order to evacuate can be
given. Beforehand,
the keypad must be enabled
and also if any of the keys on the control panel are pressed,
except for the
buzzer
(the control panel requests a code to be entered):
To enable the keypad, the access code must be entered by using the (
▲▼◄►
)
keys
:
The access code is:
27
(This must be confirmed with the ENTER key).
This operation must be performed each time an access code is requested. Once the code has been entered, all the
keys on the control panel can be used.
5. Evacuation
This function can be performed once the
keypad
has been
enabled
and by pressing the evacuation key.
IMPORTANT:
This must be confirmed with the
ENTER
key
This function activates all
sirens
and
switches
in the system. This is also shown by lighting the luminous indicator.
6. SILENCE SIRENS
When required, this function enables the sirens to be silenced. The
keypad
must be
enabled
and it is performed by
pressing the SILENCE SOUNDERS key
:
IMPORTANT:
while the luminous indicator is lit, the system’s
sirens will
NEVER
be activated.
7. RESET EVENTS
In the case of a false alarm, the user must
Reset
the alarm. With the
keypad enabled
, select the alarm to be reset
and press the
reset
key:
IMPORTANT:
when an alarm is reset, this must be confirmed
with the
ENTER
key
If the incident is a
FAULT
, this must also be
Reset
following the exact same process as explained above. If the
FAULT
reoccurs, contact the technical service.
DISCONNECT the 110~230V POWER supply and the BATTERIES before