Digital fire detection control panel
LYON
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
74
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] -
www.cofem.com
0 1 > Z : 0 0 1 L AB E L 0 1 0 1 0 0 6
A L A R M S C : B : P t :
< < 0 1 / 0 2
3.5. Assign a number to Point
By selecting option
4
assign a number to an element
the option will be the first to appear. Confirm with the
ENTER
key.
This option assigns a loop and an order number within the loop to each element.
Important:
In order to proceed with this operation, the installer must have made written note of the programming number of
each of the detectors and the loop in which they are installed.
Firstly, you will be asked for the programming number of the corresponding Point, confirmed with the
ENTER
key. Secondly, you will be asked for the assigned Point number, confirmed with the
ENTER
key
.
4. Programming verification process
It is always recommended to check that programming has been performed correctly.
Monitor
This function is number 1 on the first menu. Select with the
ENTER
key.
Firstly, you will be asked for the number of the loop and then the programming number of the element.
Check that the information shown is correct.
With the (
) arrow keys, it is possible to change from one point to another.
With the (
) arrow keys, it is possible to change from one loop to another
5. Configure Zones
The purpose of an alarm zone is to provide more complete information and to achieve greater speed when locating
an element with an alarm. The aim of a zone is to group together detectors that are located in the same area.
When an incident is detected by the control unit, pressing the (
) key will display the label of the zone to which
point belongs.
In order to configure alarm zones, it is necessary to follow the following steps:
Menu (access code 27)
4.
System configuration (access code 9000)
3
Configure
3
Configure Alarm
Zones.
You will be asked for the number of the zone to configure. Enter the number and the following menu will appear:
1
Configure zone
2
Modify Lists
3
Delete zone
4
Label
5
View configuration
B : 1 P : 7 N S : 5 5 4 6 3 T Y P E : A 3 0 X T A
L O O P : 0 0 1 A D R E S S : 0 0 1 S. N u m. :
5 5 4 6 3
D i r t : 0 0 0 % A v e r a g e : - - - S e n s i t i v : M E D
V a l u e s : [ 0 2 2 0 2 2
] L a s t : 0 0 0
0 2 2 0 2 2
Alarm zone
label