AFX SERIES® OPERATION MANUAL
SECTION 5: UNPACKING AND INSTALLATION
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 68 of 402
5.14.4
Cabinet System AC Input Connections
All input and output connections are located at the lower rear of the back of the cabinet. To
access the internal terminal blocks, the rear panel grid must be removed temporarily by
removing the screws that hold it to the cabinet’s rear. Strain reliefs for both input and
output cables are provided on the lower rear filler panel.
Note: Input and /or Output cables for grid power and load connections are NOT included
with AFX cabinets.
AC input ratings for Cabinet systems are the same as for individual AFX units. The AC input
rating is listed on the cabinet serial tag, which is located on the side of the cabinet. As
sample AFX Cabinet System label is shown below. Maximum AC input current rating is
shown per phase for the entire cabinet at low line conditions.
Note: The grid panel MUST be re-installed after all input and output wiring is installed.
INPUT VOLTAGE RATING ON SYSTEM LABEL
CAUTION: GRID DISCONNECT REQUIRED
Note that a suitable grid power disconnect switch must be provided between the grid connection
and the AFX Cabinet AC input terminal block. Consult an electrician to ensure proper local
electrical codes are used at all times.
5.14.5
Recommended AC Input Wire Strip Lengths
The following wire strip lengths are required for the AC input wires
listed.
L1, L2, L3 Wires:
11/16”, 17 mm
Neutral, Ground Wires:
3/4”, 19 mm