Error Source
Code
Category
Error Message
Possible Cause
Resolution
Front panel
Error
162
Error
CSC is always disabled
during transient in UPC
compatible mode.
Setting conflict. CSC
mode cannot be enabled
during transients
Change to AFX Mode
Front panel
Error
163
Error
Auto RMS is always
enabled in UPC
compatible mode.
Setting conflict. Auto RMS
mode cannot be disable
in UPC mode
Change to AFX Mode
Front panel
Error
164
Event
Warning: CSC is enabled
and Auto-RMS is disabled.
Output RMS may not be
regulated properly.
Notification. Load
regulation may be off
Change to AFX Mode
Front panel
Error
165
Event
Maximum AC voltage
limit was reduced due to
extended voltage range.
Notification. Extended AC
voltage range derating
implemented
Front panel
Error
166
Error
Unable to set extended
voltage because
frequency is outside the
allowed range.
Setting conflict. Extended
AC voltage mode
available over limited
frequency range
Adjust frequency to
within available range
Front panel
Error
167
Error
Power limits were
reduced due to extended
voltage range.
Setting conflict. Extended
AC voltage mode
available over limited
power range
Adjust load to within
available power range
Front panel
Error
168
Error
AC voltage set points
and/or AC voltage
maximum limit were
reduced due to extended
voltage range.
Notification. Extended AC
voltage range derating
implemented
Front panel
Error
169
Error
Unable to update set
point because it is outside
the allowed range of
extended voltage mode
Notification. Extended AC
voltage range derating
implemented
Front panel
Error
171
Error
Warning: Repeated
waveform alias.
Duplicate waveform Alias
name. Waveform alias
name already exists
Use different Alias
Front panel
Error
172
Error
Command not allowed
during power stage
firmware update.
Notification. Firmware
update for Power Stage in
progress. Command not
allowed during this time.
Wait for all firmware
updates to be completed
Front panel
Error
173
Error
Cannot change Current
RMS Overload mode with
output enable.
Setting conflict. Current
RMS overload mode can
only be enabled with
output OFF
Turn output OFF, then
enable Current RMS
Overload mode
Front panel
Error
174
Error
Strobe feature not
available in this model.
Function Strobe Output
not supported. Feature
not available
Requires AUX I/O board
Front panel
Error
175
Error
Feature not available in
this model.
Feature not available.
Requires AUX I/O board
Front panel
Error
176
Error
Set points cannot be
changed while transient
program is running.
Setting conflict.
Attempting to change
setting while transient
execution is in progress
Abort Transient Run or
wait for transient
execution to complete
Front panel
Error
180
Error
Unknown processor type
detected. Run unit
discovery to recover.
Auxiliary unit not
recognized. One of more
auxiliary units were not
recognized during
discovery
Check all parallel cables
between units. Run
parallel unit discovery
from System menu to
recover