AFX SERIES® OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS)
• All Rights Reserved • No reproduction without written authorization from PPS.
AFX Series Power Source Operation Manual
Page 198 of 402
Command Syntax
CALibrate:RESET
Description
Clears all calibration coefficients. Sending this command resets all
calibration factors to defaults. After sending this command,
programming and metering remains functional and will still meet
spec.
Parameters
None
Parameter Format
n/a
Example
CAL:RESET
Query Format
CALibrate:COEFFicients:ALL?
Description
Returns all eighteen calibration factors as a comma delimited list.
Returned Data Format
<nr1>,…,<nr1>
Query Example
CAL:FACT:ALL?
0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
Command Syntax
CALibrate:UPDATE
Description
Transfers cal factors from XML Calibration file to NVM. Required only
if calibration.xml has been modified. Alternatively, the unit can be
power cycled.
Parameters
None
Parameter Format
n/a
Example
n/a
8.3.2
UPC Specific commands.
Following commands are included for UPC compatibility mode only and don’t perform any function
other than providing query responses for use with legacy software programs.
Query Format
CALibrate:VALue:XFMRRATIO?
Query Format
CALibrate:VALue:AMPLIFIERS?
Command Syntax
CALibrate:KFACTORS <k_int_Va, k_int_Vb, k_int_Vc,
k_ext_Va, k_ext_Vb, k_ext_Vc,
k_Ia, k_Ib, k_Ic, k_oscA, k_oscB,
k_oscC>
Query Format
CALibrate:KFACTors:ALL?
8.3.3
AUX I/O Interface Calibration Commands
For a list of AUX I/O calibration commands, see Section 8.10.4, “
” on page