Maintenance and inspection
Butzbach GmbH Industrietore
Originalbedienungsanleitung NOVOSPRINT_V1
24/02/2021
35
VDE determinations, DIN sheets, technical rules of other member states to the European Economic Area
treaty) in order to be able to determine that the power-operated doors can be safety operated.
Examples of these people are qualified personnel of the manufacturer or delivery companies, the operator's
personnel who have been trained by the manufacturer or other people with corresponding expert knowledge.
Qualified individuals must make their assessment objectively from the perspective of occupational safety
without being influenced by other factors, such as financial.
9.2
Maintenance and Inspection Work
The system is equipped with devices that serve to ensure the safety and protection of the operating personnel
and the system. Therefore, the safety devices and components must be checked regularly.
9.2.1 Inspection of safety components
Safety components
Instructions
Frequency
Safety components
Main switch
Turn the switch to the ON and OFF position.
Quarterly, at least annually
Sensitive edge
Simulate a blunt object being in the detection area
of the sensitive edge during the closing operation:
The door should first stop and then reverse
direction.
Monthly
Light curtain
Simulate an object being in the detection area of
the light curtain during the closing operation: The
door should first stop and then reverse direction.
Monthly
Additional control unit
components
Check their function.
Monthly
EMERGENCY OPEN
button (for doors in exit
paths and escape
routes)
Press the button once: The normal operation is
interrupted, and the door system remains open. In
order to restore normal operation, disengage the
button.
Daily
Note! Function ability of the safety edge!
If the safety edge is not functioning properly, first check the batteries in the radio device on the door
leaves for versions with radio transmitter. Otherwise, immediately contact our
customer service.
Danger! Never disable safety devices!
Never disable safety devices or bypass them.
Do not operate the system if safety devices are damaged!