4
Fault finding
Logamax Plus GB062
18
5L
BUS-Communication fault
Step
Remedy
1.
B
Switch off the boiler.CP
B
Cut the main voltage supply.
B
Check the connection terminals at
controls and boiler.
Are the connection terminals dirty or
corroded ?
yes:
B
Clean the connection terminals.
B
Connect the cable again.
B
Switch on the boiler.
5L on display ? --> 2.
no:
B
Remove the control (thermostat) and check the
error again. If there is no error, check the control
(thermostat). Change if necessary, change it.
B
Switch on the boiler.
--> 2.
2.
B
Check the connections between the
control (thermostat) and the boiler.
Is resistance very high ?
yes:
B
Switch on the boiler.
B
Cut the main voltage supply.
B
Change the connection cable between boiler and
control (thermostat).
B
Switch on the boiler.
5L on display ? --> 2.
no:
--> 3.
3.
Electronic board (PCB) is defect.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Change the electronic board (PCB).
B
Switch on the main voltage supply.
B
Switch on the boiler.
B
END