4
Fault finding
Logamax PLus GB062
27
4C
- Heat exchanger temperature limiter or flue gas temperature limiter has tripped.
- The differential pressure switch does open when the fan runs (after ignition) (only high modulation version).
Step
Step
1.
Is the system water pressure in green
area (1 - 2 bar) ?
yes:
-->2.
no:
B
Add or correct the system water pressure.
B
Bleed the air in system.
B
Make RESET and start the boiler again.
4C ? --> 2.
2.
Is the circulation pump blocked or
problem voltage supply ?
yes:
B
Remove the blockage (turn the pump shaft).
If no result :
B
Switch off the boiler and cut the main supply.
B
Drain of he water in boiler.
B
Check the fuses. if OK, change the circulation pump.
B
Refill the system again and bleed the air.
B
Switch on the main supply and the boiler.
4C ? --> 3.
no:
--> 3.
3.
Are the flue gas temperature limiter
(STB) cables disconnected ?
yes:
B
Switch off the boiler.
B
Connect the cables.
B
Switch on the boiler.
4C ? --> 4.
no:
--> 4.
4.
B
Switch off the boiler.
B
Remove the flue gas temperature
limiter (STB) connection cables.
B
Measure the flue gas temperature
limiter (STB).resistance.
Is there circuit open?
yes:
B
Change the flue gas temperature limiter (STB).
B
Connect the cables.
B
Switch on the boiler.
4C ? --> 5.
no:
B
Connect the flue gas temperature limiter (STB) cables.
B
Switch on the boiler.
--> 5.