Fault finding
Logamax PLus GB062
35
EC
Internal fault (Internal fault in the program sequence or failure of the mains voltage).
Step
Remedy
1.
Is blinking error code in display ?
yes:
B
Reset the boiler and restart the boiler again.
EC ? --> 2.
no:
--> 2.
2.
B
Switch off the boiler.
B
Is the ignition cable connection loose
or damaged ?
yes:
B
Change the ignition cable and the connection or if
possible fix it.
B
Switch on the boiler.
EC ? --> 3.
no:
--> 3.
3.
Check the O2 CO values at min. and
max. Are the values correct ?
yes:
--> 4.
no:
B
Correct he adjustment.
EC ? --> 4.
4.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Is there any damage on securty
valve (gas valve) or connection
cable?
yes:
B
Change the connection cable to securty valve.
B
Switch on the boiler.
EC? --> 5.
no:
--> 5.
5.
Electronic board (PCB) is defect.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Change the electronic board (PCB)
B
Switch on the main voltage supply.
B
Switch on the boiler.
B
END.