4
Fault finding
Logamax PLus GB062
37
6C
306
After switching gas off : Flame is detected.
Step
Remedy
1.
B
Close the gas inlet valve.
B
Switch off the boiler.
B
Replace the gas valve.
B
Check the O2 values. If neceassary, correct it.
B
Open the gas valve again. Check it for leaks.
B
Switch on the main voltage supply.
B
Press the RESET button and start the boiler again.
B
Switch on the boiler.
6C ? --> 2.
2.
Cable harness is defect.
B
Switch off the boiler.
B
Change the cable harness.
B
Switch on the boiler.
B
Press the RESET button and start the boiler again.
6C ? --> 3.
3.
Electronic board (PCB) is defect.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Change the electronic board (PCB)
B
Switch on the main voltage supply.
B
Switch on the boiler.
B