Service menu settings
Logamax PLus GB062
13
A.b
DHW temperature (Combi version)
This service function allows you to display the DHW temperature.
A.C
Temperature at cylinder tempera-
ture sensor (system version)
This service function allows you to display the temperature in the DHW cyl-
inder.
b.F
DHW heating delay (solar mode)
Heating will be suppressed until the DHW temperature sensor detects that
the water preheated by solar energy has reached the required outlet tem-
perature. Set the heating delay in accordance with system conditions.
The start delay can be set between 0 - 50 seconds.
Default setting is 0 (disabled).
F.2
Ionisation current
•
with running boiler (burner) :
–
>
20 = OK
–
< 20 = faulty
F.3
Permanent operation mode (chim-
niy sweeper)
Possible displays are:
•
0
: normal operation mode
•
1: operation in max output for 15 minutes
Service function
Possible settings/comments/displays
Tab. 4
Menu 2