4
Fault finding
Logamax PLus GB062
19
CP
System boiler: Cylinder / tank temperature sensor.
Step
Remedy
1.
Check the tank temperature sensor for
breaks or short circuits.
B
Switch off the boiler.
B
Remove the NTC of terminal.
B
Measure the electrical resistance of Tank-
NTC (in
Ω
) (see NTC tables).
Is the resistance value correct ?
yes:
--> 2.
no:
B
Change the Sensor (NTC).
B
Switch on the boiler.
CP on display ?
-->2.
2.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Check the soft code and boiler type via
Service function E.1 and 4.E.
Is it correct ?
yes
B
Switch on the boiler.
CP on display ?
-->3.
no:
B
Correct the right boiler type code.
CP on display ?
-->3.
3.
Check the NTC cables.
B
Is there any damages or short circuit or
break ?
yes:
B
Change the cable/NTC.
B
Switch on the boiler.
CP on display ?
-->4.
no:
--> 4.
4.
Electronic board (PCB) is defect.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Change the electronic board (PCB).
B
Switch on the main voltage supply.
B
Switch on the boiler.
B
END