Fault finding
Logamax Plus GB062
26
4Y
Flow temperature sensor (CH-NTC) faulty.
Step
Remedy
1.
Check the flow temperature sensor for
damages.
B
Switch off the boiler.4C
B
Remove the Socket of NTC.
B
Measure the electrical resistance of
CH-NTC (in
Ω
) (see NTC tables).
Is the resistance value correct ?
yes:
--> 2.
no:
B
Change the Sensor.
B
Switch on the boiler.
4Y on display ?
-->2.
2.
Check the NTC cables for damages.
B
Switch off the boiler.
B
In case of CH-NTC is changed :
- Remove the NTC socket.
- Measure the NTC resistance.
- Connect the socket again.
B
Remove the big socket (20 Pole) on
PCB.
B
Measure the NTC resistance (
Ω
) on
big socket (PCB side).
Are measured resistance values on
NTC and socket side different ?
yes:
B
Change the cable haarness.
B
Switch on the boiler.
4Y on display ?
-->3.
no:
--> 3.
3.
Electronic board (PCB) is defect.
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Change the electronic board (PCB).
B
Switch on the main voltage supply.
B
Switch on the boiler.
B
END