4
Fault finding
Logamax PLus GB062
25
5.
Is external temperature limiter (e.g.
TB1) triggered ?
yes:
B
Switch off the boiler.
B
Check the reason for the
external temperature
limiter
triggering and correct it.
Info :
Max flow temperature can be adjusted in
servi2E function 1.2b. It should be 5 K below of
external temperature limiter and a d4Yistan2E 2
m from boiler to external temperature limiter.
B
Reset the external temperature limiter.
B
Switch on the boiler.
8Y ? --> 6.
no:
--> 6.
6.
B
Switch off the boiler.
Is the bridge in connection terminal
installed ?
yes:
-- > 7.
no:
B
Install the bridge.
B
Switch on the boiler.
8Y ? --> 7.
7.
External temperature limiter is locked or
defect ?
B
Switch off the boiler.
B
Cut the main voltage supply.
B
Reset or change the external temperature limiter.
B
Switch on the main voltage supply.
B
Switch on the boiler.
8Y
External switching contact triggered.
Step
Remedy