3
Service menu settings
Logamax Plus GB062
10
4.b
max pre heat temperature for
comfort function (combi)
max DHW pre heat temperature for comfort function.
The following settings are possible:
•
40 … 65 ºC
Default setting : 62 º
4.E
Boiler type
It will be detected automaticly of DHW or tank NTC and shown in display.
Possible values:
•
0 : only heating
•
1 : Combi
•
2 : Tank with NTC (system boiler)
4.F
Siphon filling mode
Possible settings:
•
0 : Off
•
1 : On with min output (factory setting)
•
2 : On with changed min CH output
5.A
Reset service reminder
If you see this symbol, you can reset to “0” after inspection.
5.b
Fan overrun time
Time intervall for the maintanence (month)
0 = Off
1 .. 72 = Time (Month)
5.F
Inspection intervall
If you see this symbol, you can reset to “0” after inspection.
6.A
Calling up the last fault saved
The function enables you to retrieve the last fault stored.
The service function is reset at 00.
6.C
Setpoint value of the tempera-
ture from EMS-BUS
6.d
Current turbine flow rate (combi)
The current turbine flow rate is displayed.
Possible displays are:
•
0.0. - 20.0. l/min
7.A
Backlight of LCD
The following settings are possible:
•
00: Off
•
01: on
Default setting : 00.
7.C
Minimum DHW flow rate
DHW heating is activated if amounts above this value are drawn off.
The following settings are possible (x 0,1):
•
25 … 50 litres per minute
Default setting : 25 l/min.
Service function
Possible settings/display
Tab. 3
Menu 1