4
Fault finding
Logamax PLus GB062
15
4
Fault finding
4.1
Explanations of faults table
Each title of the table shows the error code in the display and
at the same time the cause of the error in general. To repair
any possible fault in the device, follow the troubleshooting
steps in order until the fault is detected.
4.2
Fault group definition
Shown failures are divided in diffrent category :
•
RUN
: Fault does not block the burner.
•
WAIT
: Fault blocks the burner until faults removes.
•
BLOCK
: Fault blocks the burner until mains supply off
(volatile lockout).
•
LOCK
: Faults blocks the burner (nonvolatile lockout).
•
RESET
: Fault causes a board reset.
•
HIST
: Fault code is only stored in EEPROM fault history.
Failure Code
Cause
Code
Failure
Category
Failure description
Page
CL
324
RUN
Hot water temperature sensor is faulty.
17
5L
323
RUN
BUS-Communication fault.
19
CP
326
RUN
WBC...D appliances (system boiler): Cylinder/tank temperature sensor.
20
3Y
334
WAIT
The differential pressure switch is open before ignition (during self
check) (only high modulation version).
20
3C
217
WAIT
Fan not running.
20
2E
207
WAIT
Heating system charge pressure is too low.
23
8Y
232
WAIT
External switching contact triggered.
24
4Y
223
WAIT
Flow temperature sensor (CH-NTC) faulty.
26
4C
224
LOCK
- Heat exchanger temperature limiter or flue gas temperature limiter has
tripped.
- The differential pressure switch does open when the fan runs (after
ignition) (only high modulation version).
30
6A
227
LOCK
Flame not detected.
30
EC
256
LOCK
Internal fault.
35
6C
228
LOCK
Flame detected even when the burner is switched off.
36
6C
308
LOCK
After switching gas off : Flame is detected
.
37
EP
327
LOCK
The “OK” button was actually pressed for at least 5 seconds (= reset).
38
WAIT
Gradient Monitoring.
43
P
78
WAIT
Appliance code not defined.
44
Tab. 7
Failure codes shown in display