6
Inspection and maintanance
Logamax Plus GB062
50
6.6
Checking the strainer in the cold water pipe
B
Remove the clip.
B
Pull out the pressure relief valve.
Fig. 18 Removing the pressure relief valve (heating circuit)
1. Remove the clip.
2. Pull out the insert.
3. Check strainer for contamination.
Fig. 19 Checking the strainer in the cold water pipe
6.7
GB062..K.. (Combi) appliances: Check the
plate heat exchanger
If the DHW output is insufficient :
B
Check the strainer in the cold water pipe for contamination.
B
Descale the plate heat exchanger with scale removal
agent approved for stainless steel (1.4401).
-or-
B
Remove plate heat exchanger and replace.
1. Remove the screw.
2. Remove the plate heat exchanger.
Fig. 20
Removing the plate heat exchanger
6.8
Checking the expansion vessel
The expansion vessel must be checked every year.
B
Depressurise the device.
B
Adjust the pre-charge pressure of the expansion vessel to
the static head of the heating systems, if necessary.
6.9
Setting the heating system operating
pressure
If the indicator is below 1 bar when the system is cold :
1.
2.
0 010 006 637-001
1.
2.
3.
0 010 006 636-001
Display on the pressure gauge
1 bar
Minimum filling pressure (when sys-
tem is cold)
1 - 2 bar
Optimal charge pressure
3 bar
Maximum charge pressure at maxi-
mum heating water temperature must
not be exceeded (pressure relief
valve will release).
Tab. 13
0 010 005 834-001
1.
2.