98
VIDEO DOOR ENTRY SYSTEM -
CONFIGURATION
D45
General configuration concept
physical conFiguration (installation)
The devices may be configured in three ways:
n
Use of physical configurators: this means placing the
right numbered configurators in the devices in the right
position (depending on the design of the configuration) .
n
Define a procedure of configuration of each device that
uses its resources (keypad, LCD, LEDs, etc . ) in order assign
to the device the designated number .
n
Use the PC on the field to download the results of the
design configuration done on a PC, on to each device
using its MAC address .
ToTal nuMber oF aparTMenTs
in The insTallaTion:
virTually no liMiTs
Number of apt. for each “district” (AS02:
LAN-8Wire interface)
4.000 apt. or villas.
Total number of units/riser for each
district
400
Total number of apt./villas for each riser:
800 (if only 1 handset in each apt.)
Total number of apt./villas for each riser:
400 (if only 2 handsets in each apt.)
Total number of apt./villas for each riser:
265 (if only 3 handsets in each apt.)
Total number of apt./villas for each riser:
800 (up to 5 handsets in each apt. with D45
apt. interface)
conFiguration moDe For the whole system
Two configuration modes available, configuration mode
1 and configuration mode 2 . The main characteristics for
each configuration mode are described below:
*1*: Below are the rules for system configuration (Mode 1) .
#FF
For each riser
#ii
For each Floor
can sysTeM conFiguraTion Mode 1
be used?
≤ 20
≤4
YES,
but it is necessary to calculate the total number of
handsets for whole system according to Mode 1
configuration. If the total number calculated is 4000
or less, Mode 1 configuration is possible, if the total
number is over 4000, Mode 2 must be considered.
> 20
≤ 4
NO
≤20
> 4
NO
> 20
> 4
NO
*2*: Below is an example explaining the rules for system
configuration (Mode 2):
For example: if the highest building of a project has 25 floors,
and the max . number of apartment for floor is 8, with 15
risers in total . Then for mode 2, the #FF should be 25, while
#II should be 8 . Make the calculations according to following
table to judge if mode 2 configuration can be used .
#FF For
each riser
#ii For
each
Floor
ToTal
riser
can sysTeM con-
FiguraTion Mode 2 be
used?
25
8
15
25*8*15=3000
3000<4000
30 - 25*8*30=6000
6000>4000
how to choose the right conFiguration moDe
n
The biggest #FF number in the whole system ≤ 20, the
biggest #II number in the whole system ≤4, and the
number of risers ≤ 50: system configuration Mode 1 is
recommended .
n
If the biggest #FF number in whole system is more
than 20, or the biggest #II number is more than 4,
please use system configuration Mode 1 to set #FF
(choose the biggest #FF number in the system) and
#II (choose the biggest #II number in the system), then
calculate the total number of handsets in the system .
If the total number (#FF * #II * R ) is 4000 or less, use
system configuration Mode 2 .
system conFiguration moDes
There are 3 possible system configuration modes:
n
Resistor configuration
n
Local keyboard configuration
n
Configuration using the configuration software, then
download to the devices using the RS232 port
Remarks:
For the 3 above configuration modes, the parameters to
configure are the same, therefore it is not necessary to
describe the configuration procedures separately . Below is
an explanation of the resistor configuration as an example .
The keyboard configuration is described in the product
manual . The configuration using the RS232 port is described
in the configuration software manual .