14.2
Digital outputs
14.2.1
Digital Outputs (Safety Technology L Options)
The digital outputs are compatible with digital inputs of types 1, 2 and 3
(IEC 61131).
Fig. 14-3:
Symbol
Data
Unit
Min.
Max.
Supply voltage (U
ext
)
V
19,2
30
Current consumption (I
ext
)
mA
700
Output voltage ON
V
18,2
30
Output voltage OFF
V
5
Output current ON
mA
350
Allowed energy content of con‐
nected inductive loads, e.g. re‐
lay coils; only allowed as single
pulse
mJ
400
Short circuit protection
Available
Overload protection
Available
Tab. 14-5:
Digital Outputs (Safety Technology L Options)