4.3.3
Mounting position
Mounting positions of components
Risk of damage to the components by incor‐
rect mounting position!
NOTICE
Only operate the components in their allowed mounting positions. The al‐
lowed mounting positions are specified in the technical data of the compo‐
nents.
For supply units and drive controllers installed in control cabinets, only the
mounting position G1 is usually allowed.
Some components can also be operated in mounting positions other than G1.
The allowed mounting positions are specified in the technical data of the
component.
Mounting positions
The allowed mounting positions are specified with G1, G2, G3, G4 or G5 in
the technical data of the components.
Mounting
position
Description
G1
Normal mounting position
The air heated inside the component can flow unimpe‐
ded vertically upward. In the case of components with
integrated fans, the natural convection supports the
forced cooling air current.
1.
Mounting surface
2.
Outgoing, heated air
3.
Component
4.
Fan within the component (forces the cooling air
current)
5.
Cooling air
G2
180° to normal mounting position
G3
90° to normal mounting position
G4
bottom mounting; mounting surface on the bottom
G5
top mounting; mounting surface at the top
Tab. 4-11:
Mounting positions
Bosch Rexroth AG
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
60/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
General data and specifications