Fig. 6-2:
Connection of Contact Bars
Notes on Installation
If in special cases it is not possible to use the contact bars provided to estab‐
lish the connection, the connection must be established using the shortest
possible twisted wires.
Risk of damage by voltage arcing!
NOTICE
Insulate ring terminals and lines with a heat-shrinkable sleeve. Afterwards,
only strip the insulation of the contact surface of the ring terminal.
When connecting the lines, make sure the polarity is correct.
Length of twisted wire
Max. 2 m
Line cross section
Min. 10 mm
2
,
but not smaller than cross section of supply feed‐
er
Line protection
By means of fuses in the mains connection
Dielectric strength of single
strand against ground
≥ 750 V (e.g.: strand type – H07)
Tab. 6-13:
DC Bus Line
Bosch Rexroth AG
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
138/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Connection points