Mains voltage
Mains voltage supply data
Description
Symbol
Unit
KMV03.1R-B0007-P-D7-ET-NNNN
Mains frequency
f
LN
Hz
50...60
Mains frequency tolerance
Hz
±2
Maximum allowed mains frequen‐
cy change
Δf
LN
/Δt
Hz/s
1
Rotary field condition
None
Short circuit current rating
SCCR
A rms
42000
Nominal mains voltage
U
LN_nenn
V
3 AC 400
Three-phase mains voltage at TN-
S, TN-C, TT mains
U
LN
V
3 AC 380…500
Three-phase mains voltage at IT
mains
1)
U
LN
V
tbd
Three-phase mains voltage at
Corner-grounded-Delta mains
2)
U
LN
V
tbd
Tolerance rated input voltage U
LN
%
±10
Minimum inductance of mains
supply (mains phase inductance)
3)
L
min
µH
50
Assigned mains filter with integra‐
ted mains choke
KNK03.1A-NR-B0012-P-U226-A4-NNNN
Minimum short circuit power of the
mains for failure-free operation
S
k_min
MVA
tbd
Inrush current
I
L_trans_max
_on
A
tbd
Maximum allowed ON-OFF cycles
per minute
4)
1
Power factor TPF (λ
L
) at P
DC_cont
with mains choke; U
LN_nenn
TPF
tbd
Power factor of fundam. compo‐
nent DPF at P
DC_cont
with mains
choke
cosφ
h1
tbd
Mains connection power at
P
DC_cont
; U
LN_nenn
with mains choke
S
LN
kVA
15.00
Rated input current
I
LN
A
12
Last modification: 2016-03-08
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
Bosch Rexroth AG
95/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Technical data of the components
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01