6.6.11
XG14, mains voltage synchronization
View
Connection Function
L1
Connection to mains filter(XG14.L1)
L2
Connection to mains filter (XG14.L2)
L3
Connection to mains filter (XG14.L3)
Tab. 6-58:
Pin assignment
Mechanical data
Screw terminal (connector)
Unit
max.
Connection cable
Stranded wire
mm
2
6
AWG
8
Stripped length
mm
10
Tightening torque
Nm
0.8
Tab. 6-59:
Mechanical data
Electrical data
Screw terminal (connector)
Unit
Value
Nominal current
A
41
Rated voltage
V
1000
Tab. 6-60:
Electrical data
Cables
Description
Value
Order type
Maximum allowed length
1 m
Tab. 6-61:
Cables
Bosch Rexroth AG
DOK-INDRV*-KCU02+KSM02-PR03-EN-P
184/337
Rexroth IndraDrive Mi Drive Systems with KCU02 KSM02, KMS02/03, KMV03, KNK03
Connection points
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01