Installation
WDP3-01X Ident-Nr.: 00441109760
2-8/1
ATTENTION
Connect the shield of the motor cable after the following assembly
instruction!
Installing the motor cable
The following items required for installing the motor cable on the side of
the device are included in the accessory bag:
Installing the terminal angle
DANGER
Electric shock from high voltage!
If longer screws are used, they may contact live parts. This may
result in fatal injury.
The terminal angle is fastened to the bottom of the device with the
screws and serrated washers supplied with the device. Correct installa-
tion of the terminal angle is extremely important for grounding the motor
cable shield and for strain relief.
Qty.
Designation
1
Terminal angle
1
Shield terminal
1
Screw M4 x 8
2
Screw M3 x 8 with serrated Washer
1
Serrated washer M4
(connection of second protective conductor)
DANGER
Electrical device with higher deflection current > 3,5mA.
Connection of a second protective conductor absolutely necessary.
Please note minimum cross-section according to IEC 60364-5-54.
Screw M4 x 8
Screw M3 x 8
Fig. 2-8 Installing the terminal angle