Commissioning
EL125x, EL2258
185
Version: 2.5
Index 1605 MTO RxPDO-Map Outputs 5x Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
1605:0
MTO RxPDO-Map
Outputs 5x Ch.2
PDO Mapping RxPDO 6
UINT8
RO
0x13 (19
dec
)
1605:01
SubIndex 001
1. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x01 (Output buffer reset))
UINT32
RO
0x7011:01, 1
1605:02
SubIndex 002
2. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x02 (Manual output state))
UINT32
RO
0x7011:02, 1
1605:03
SubIndex 003
3. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x03 (Force order))
UINT32
RO
0x7011:03, 1
1605:04
SubIndex 004
4. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x04 (Enable manual operation))
UINT32
RO
0x7011:04, 1
1605:05
SubIndex 005
5. PDO Mapping entry (4 bits align)
UINT32
RO
0x0000:00, 4
1605:06
SubIndex 006
6. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x09 (Output order counter))
UINT32
RO
0x7011:09, 8
1605:07
SubIndex 007
7. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x11 (No of output events))
UINT32
RO
0x7011:11, 8
1605:08
SubIndex 008
8. PDO Mapping entry (8 bits align)
UINT32
RO
0x0000:00, 8
1605:09
SubIndex 009
9. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x21 (Output event state 1))
UINT32
RO
0x7011:21, 1
1605:0A
SubIndex 010
10. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x22 (Output event state 2))
UINT32
RO
0x7011:22, 1
1605:0B
SubIndex 011
11. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x23 (Output event state 3))
UINT32
RO
0x7011:23, 1
1605:0C
SubIndex 012
12. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x24 (Output event state 4))
UINT32
RO
0x7011:24, 1
1605:0D
SubIndex 013
13. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x25 (Output event state 5))
UINT32
RO
0x7011:25, 1
1605:0E
SubIndex 014
14. PDO Mapping entry (27 bits align)
UINT32
RO
0x0000:00, 27
1605:0F
SubIndex 015
15. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x41 (Output event time 1))
UINT32
RO
0x7011:41, 32
1605:10
SubIndex 016
16. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x42 (Output event time 2))
UINT32
RO
0x7011:42, 32
1605:11
SubIndex 017
17. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x43 (Output event time 3))
UINT32
RO
0x7011:43, 32
1605:12
SubIndex 018
18. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x44 (Output event time 4))
UINT32
RO
0x7011:44, 32
1605:13
SubIndex 019
19. PDO Mapping entry (object 0x7011 (MTO outputs
Ch.2), entry 0x45 (Output event time 5))
UINT32
RO
0x7011:45, 32
Содержание EL1258
Страница 2: ......
Страница 6: ...Table of contents EL125x EL2258 6 Version 2 5...
Страница 42: ...Mounting and wiring EL125x EL2258 42 Version 2 5 Fig 36 Other installation positions...
Страница 76: ...Commissioning EL125x EL2258 76 Version 2 5 Fig 86 Incorrect driver settings for the Ethernet port...