Commissioning
EL125x, EL2258
139
Version: 2.5
Index 6pp0 TSI Inputs (for 08 ≤ pp ≤ 0F; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
6pp0:0
TSI Inputs
UINT8
RO
0x00 (0
dec
)
6pp0:01
Input
Current input status
BOOLEAN
RO
0x00 (0
dec
)
6pp0:09
Status
Bit0: Is set for one cycle if a rising edge was detected.
Bit1: Is set for one cycle if a falling edge was detected.
UINT8
RO
0x00 (0
dec
)
6pp0:41
LatchPos
Timestamp of the rising edge
UINT64
RO
6pp0:42
LatchNeg
Timestamp of the falling edge
UINT64
RO
Index F611 DEV Inputs
Index (hex) Name
Meaning
Data type
Flags
Default
F611:0
DEV Inputs
UINT8
RO
0x21 (33
dec
)
F611:02
Undervoltage Up
The nominal operating voltage at the power contacts
was significantly below the minimum value.
BOOLEAN
RO
0x00 (0
dec
)
F611:03
Overtemperature
Overtemperature fault: The temperature of the input or
output blocks is too high. For output terminals check
whether one of the channels is affected by a short cir-
cuit.
BOOLEAN
RO
0x00 (0
dec
)
F611:04
Checksum error
An error occurred in the internal data transfer
BOOLEAN
RO
0x00 (0
dec
)
F611:21
SysTime
DC timestamp of the last input mapping. This time-
stamp should not be used as reference.
(information
on DC reference times). [
}
133]
UINT64
RO
6.8.1.1.4
Output data
Index 7pp0 MTI outputs (for 00 ≤ pp ≤ 07; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
7pp0:0
MTI outputs
UINT8
RO
0x00 (0
dec
)
7pp0:01
Input buffer reset
Removes all elements from the buffer
Clearing can be achieved through a rising edge or con-
tinuously by applying 1 at this bit. The behavior can be
parameterized via the CoE object
0x8pp0:11 [
}
137]
("Buffer reset behavior").
BOOLEAN
RO
0x00 (0
dec
)
7pp0:11
Input order counter
This bit indicates to the terminal that the input events
were accepted from the process image and the termi-
nal can copy a new set of input events from the buffer
into the process image during the next cycle
(see buf-
fer mode). [
}
122]
UINT8
RO
0x00 (0
dec
)
6.8.1.1.5
Diagnostic data
Index App0 MTI Diag data (for 00 ≤ pp ≤ 07; Ch. 1 to Ch. 8)
Index (hex) Name
Meaning
Data type
Flags
Default
App0:0
MTI Diag data
UINT8
RO
0x02 (2
dec
)
App0:01
Overtemperature
The internal terminal temperature is above the valid
range. For terminals with output channels check the
outputs for short circuit.
BOOLEAN
RO
0x00 (0
dec
)
App0:02
Undervoltage
The voltage at the power contacts is outside the valid
range.
BOOLEAN
RO
0x00 (0
dec
)
Index A001 MTI common Diag data
Index (hex) Name
Meaning
Data type
Flags
Default
A001:0
MTI common Diag
data
UINT8
RO
0x11 (17
dec
)
A001:11
Checksum error
counter
An error occurred in the internal data transfer
UINT16
RO
0x0000 (0
dec
)
Содержание EL1258