Commissioning
EL125x, EL2258
132
Version: 2.5
6.6.3
Commissioning in compatibility mode EL2252
The multi-timestamp terminals can also be operated in compatibility mode with regard to the EL2252. The
following settings are required:
Procedure:
- The changeover should only be implemented via the
predefined PDO
:
Fig. 167: Predefined PDOs for compatibility mode
- CoE 0x70n0:0 MTO outputs Ch.n (n=8...F) can be used for configuration, similar to the EL2252. In
addition the EL2252 offers a tristate PDO for high-resistance switching of the channels. This PDO is not
available for the EL2258.
0x70n0:0 MTO
Output Ch.
n=8...F
Name
Entry
Description
70n1:01
Output
Activates output 0 V/24 V of channel n=1..8
0x70n0:01 FALSE
0 V present at the output
0x70n0:01 TRUE
24 V present at the output
70n1:11
Activate
This byte activates a new start time in the terminal
through the transition 0 --> 3
70n0:41
Start Time
64-bit value of the next desired switching event
Note
Free PDO selection
No provision is made for free arrangement of the respective PDOs in compatibility mode.